What is a fire collar?
- Every seal labelled and photographed
- BM TRADA / FIRAS-certificated contractors
- Written price before any work
A steel or plastic ring, a few centimetres deep, that clamps round a plastic pipe where it passes through a fire wall or floor. Inside the ring is a band of intumescent material. In a fire the pipe softens and starts to burn away, the band swells to many times its thickness, and it crushes the soft pipe shut and fills the hole it leaves behind.
On a concrete floor the collar is usually screwed to the underside, round the pipe, with steel anchors into the slab. On a wall it often goes on both faces. The collar size must match the outside diameter of the pipe, and the collar must have been tested with that kind of pipe in that kind of wall or floor. A collar tested on a PVC soil pipe in a concrete slab tells you nothing about a polypropylene waste through a timber floor.
Missing collars are common where a plumber has replaced a length of pipe. The collar comes off, the new pipe goes in and the collar stays in the van. If you see a plastic pipe passing through a riser floor with only mortar or mastic round it, look underneath for a collar. If there is none, the hole needs one.

Send the postcode, the type of building and the line from the assessment, or a photo of the gap. We reply with what it needs and a written price.